Cedar Flats Commerce Center
Stage
Comments Returned
Submittal
Comments Returned
1st Submittal
IN-NET
Awaiting Submittal
Submitted
Under Review
Reviewed
Comments Returned
Approved
Group:
4 of 5 comments
1st Submittal
· Site Plan & Utility Set
4 open
4 comments
▼
4
1
reply
reply
Engineering
· Dana Kowalski
Site Plan & Utility Set
Clarification
📄 U-201
Comment Responded To
✓ Accepted into active queue
Confirm sanitary main invert elevations at the MH 3 tie-in.
Sep 13, 2026
Assign
3
Planning
· Alex Moreno
Site Plan & Utility Set
Should Correct
📄 L-101
Action Required
✓ Accepted into active queue
Provide additional buffer plantings along the north property line.
Sep 13, 2026
JR
Jordan Reyes2
Engineering
· Dana Kowalski
Site Plan & Utility Set
Must Correct
📄 C-301
Action Required
✓ Accepted into active queue
Detention pond outlet structure does not pass the 100-year release rate. Revise.
Sep 13, 2026
JR
Jordan Reyes1
Public Works
· Sam Okafor
Site Plan & Utility Set
Must Correct
📄 C-102
Action Required
✓ Accepted into active queue
Extend the westbound right-turn lane taper to meet the 150 ft standard.
Sep 13, 2026
JR
Jordan Reyes